The “Digital Output 4 channels Power Relay” card provides 4 “dry contact” relays.
• Rated relay switching : 5A at 130 VAC (resistive load)
• Turn on time: 5 mS
• Turn off time: 2 mS
• 4 KV Transient isolation with backplane
• 1KV Transient isolation Relay to Relay
|
|
 |
|
|
|
|
 |
|
The “Digital Input 8 channel DC” Card provides 8 contact closure inputs.
Applications: end course, push buttons, voltage detection, ...
• Voltage range: 12 to 48 VDC
• Voltage rating: 60 VDC
• Common Ground (source)
• Threshold level:voltage: ±5 VDC
• Turn on time: 5 mS
• Turn off time: 5 mS
• Overvoltage protection: ±60 V
• 4 KV Transient isolation with backplane
|
 |
 |
|
The “Digital Input 4 AC” card provides versatile connections for 4 AC and/or DC voltage
input. The inputs can be wired as isolated input-to-input and/or common ground (Source)
and/or common positive (Sink).
• Voltage range: 12 to 48 VAC/DC
• Voltage rating: 60 VAC/DC
• Switching threshold level: ±5 V
• 50 & 60 Hz compliant
• Turn on time: 5 mS
• Turn off time: 25 mS
• Input protection: ±60 V
• 4 KV Transient isolation with backplane
• 1 KV Transient isolation chanel-to-channel |
|
 |
|
|
|
|
 |
|
The “Digital Output 4 channels Analog Relay” card provides 4 “dry contact” low signal
relays. Main applications: Audio, low signal
• Rated load : 1A/120 VAC or 2A/130 VDC (resistive load)
• Turn on/off time: 3 mS
• 4 KV Transient isolation with backplane
• 1KV Transient isolation relay-to-relay |
 |
 |
|
The “Digital Output 4 channels Bistable Relay” card provides 4 “dry contact” low signal
relays. The Bistable relays will keep their current state if the I/O CardCage loses its power
or is being reset. The state of each relay can be read at anytime
• Rated load : 1A/120 VAC or 2A/130 VDC (resistive load)
• Turn on/off time: 3 mS
• 4 KV Transient isolation with backplane
• 1KV Transient isolation Relay-to-Relay |
|
 |
|
|
|
|
 |
|
The “Digital Output 8 channels SinK” card provides 8 common ground outputs.
Main applications: Low Power Solenoid, LED, lamp, Relay, High speed and repetitive
commutation
• Common ground (Sink)
• Voltage range: 5 to 30 VDC
• Voltage rating: 50VDC
• Maximum current driver: 0,3A /30 VDC (resistive load)
• Protected by resettable Fuses
• 4 KV Transient isolation with backplane |
 |
 |
|
The “Analog Input 8 channel Ratiometric” converter card provides 8 analog ratiometric
inputs
Main applications: Potentiometers reader, analog detection, sensors, ...
• Resolution: 8 bits
• Sampling rate:
• Voltage reference available on pin #1
• Input voltage range: 0 to 5 VDC
• Input voltage protection: ±30 VDC
• No Isolation with the backplane |
|
 |
|
|
|
|
 |
|
The “Analog Output 8 channel Digital to Analog” converter card provide connections for
Octal analog output.
Main applications: CV generation, 0-10V Dimmer, Motor control, ...
• DAC resolution: 8 bits
• Output voltage range: 0 -10 VDC
• Maximum current driver: 4 mA/channel
• Short circuit protection: Indefinitely
• Overvoltage protection: ±30 V
• No Isolation with the backplane |
 |
|
|
 |
|